EF20 Fixed Gas Detector

EF20 Fixed Gas Detector

EF20 Fixed Point-Type Combustible Gas Detector is an intelligent combustible gas detector independently developed by our company. It can output 4~20mA current signals and RS485 digital signals with real-time concentration display...

Quote Now

Introduction

EF20 Fixed Point-Type Combustible Gas Detector is an intelligent combustible gas detector independently developed by our company. It can output 4~20mA current signals and RS485 digital signals with real-time concentration display, and supports customization for various target gases.

This detector adopts catalytic combustion sensors, featuring strong anti-interference capability, high measurement accuracy and high intelligence level. On-site monitoring and alarm functions can be activated simply via basic configuration.

Features

Adopts advanced micro-power consumption sensor technology.

On-site gas concentration display enables field operators to grasp real-time conditions promptly.

Supports standard 4~20mA current signal output and RS485 output with MODBUS protocol.

LED indicators display working status, including normal operation, primary alarm, secondary alarm and fault alarm.

Equipped with an explosion-proof housing, applicable to a wide range of working scenarios.

Application

Specifications

Parameter Specification
Sampling Method Natural diffusion
Operating Voltage DC 24V±6V
Power Consumption ≤3W
Operating Mode Continuous detection
Status Indication Yellow indicates fault, red indicates concentration alarm, green indicates normal operation
Operation Mode Infrared remote control
Response Time (t90) ≤30s (combustible gas); ≤60s (toxic gas);
Operating Temperature -40℃ ~ +70℃ (combustible gas); -10℃ ~ +50℃ (toxic gas);
Operating Humidity ≤95%RH (non-condensing)
Explosion Protection Method Flameproof type
Explosion Protection Rating Ex d ⅡC T6 Gb
Ingress Protection Rating IP65
Ambient Pressure 86kPa ~ 106kPa
Output Signal 4~20mA / RS485 / PowerBus two-wire / NBIOT
Explosion-proof Connection Thread M20×1.5 (internal pipe thread) or G3/4 internal thread (adapter optional)
Cable Requirements ≥1.5 mm²×3 shielded cable, cable outer diameter required between 6mm~9mm (4~20mA) / 1.5 mm²×4 (RS485) / 1.5 mm²×2 (PowerBus two-wire)
Maximum Distance Between Detector and Host ≤1000m
Sensor Service Life Three years (catalytic combustion sensor for combustible gas, five years for optical principle, two years for electrochemical toxic gas)
Product Dimensions 170mm × 150mm × 85mm
Weight Approx. 1.5Kg.
Home Product Solution About